Permit: T02EL02147

Parcel: 110030890

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL02147

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/03/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
02/26/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*ALL STRANDS OF CONDUCTORS TO BE UNDER TERMINAL CONNECTION.
2.) PLEASE FILL UNUSED OPENINGS IN SUBPANEL.
02/21/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*PREVIOUS NOTE STATED FEEDS TO SUBPANEL NOT AC UNIT, #1WIRE IS GOOD FOR 130 AMPS ONLY THESE ARE CONDUCTORS WHICH NEED CORRECT PROTECTION. PLEASE GET THIS DONE AS SOON AS POSSIBLE DO NOT ENERGIZE. INSTALL A 100AMP BREAKER FOR SUB PANEL.
02/20/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*PLEASE CALL 791-5550 EXT 1136 FOR MEETING.
02/11/2003 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
THIS WORK IS TO BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AS PER THE REGISTRAR OF CONTRACTORS. APPLICANT IS NOT OWNER OR RESIDENT.
THIS IS AN UNSAFE INSTALLATION. THE FEEDS FOR THE SUB PANEL. NEED TO BE CORRECTED IMMEDIATLY. YOU OR POWER WILL BE SHUT OFF.
02/07/2003 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) SUPPORT CONDUIT TO A/C & TIGHTEN FITTINGS.
2.) PLEASE LABEL ALL BREAKERS.
3.) CONDUCTORS TO BREAKERS TO BE SIZED PER AMPACITY ALLOWED BY MANUFACTURE AND TABEL 310-16.
11/27/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*CALL FOR FINAL WHEN CHANGE OVER COMPLETED.
11/22/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0935*1.) NO PROGRESS AS OF INSP. ON 11/8/02 2.) A RE INSPECTION FEE IS ASSESED, PLEASE PAY RE INSPECTION FEE 201 N STONE PRIOR. TO FUTURE INSPECTIONS.
11/13/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*
11/05/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) SUPPORT RISER CONDUIT WITHIN 3' OF SERVICE ENCLOSURE, MUST USE MIN 1/4" BOLTS.
2.) SUPPORT 2" CONDUIT RUN UNDER PANEL.