Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL02147
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/03/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* | |
02/26/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*ALL STRANDS OF CONDUCTORS TO BE UNDER TERMINAL CONNECTION. 2.) PLEASE FILL UNUSED OPENINGS IN SUBPANEL. |
|
02/21/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PREVIOUS NOTE STATED FEEDS TO SUBPANEL NOT AC UNIT, #1WIRE IS GOOD FOR 130 AMPS ONLY THESE ARE CONDUCTORS WHICH NEED CORRECT PROTECTION. PLEASE GET THIS DONE AS SOON AS POSSIBLE DO NOT ENERGIZE. INSTALL A 100AMP BREAKER FOR SUB PANEL. | |
02/20/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*PLEASE CALL 791-5550 EXT 1136 FOR MEETING. | |
02/11/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999* THIS WORK IS TO BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR AS PER THE REGISTRAR OF CONTRACTORS. APPLICANT IS NOT OWNER OR RESIDENT. THIS IS AN UNSAFE INSTALLATION. THE FEEDS FOR THE SUB PANEL. NEED TO BE CORRECTED IMMEDIATLY. YOU OR POWER WILL BE SHUT OFF. |
|
02/07/2003 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) SUPPORT CONDUIT TO A/C & TIGHTEN FITTINGS. 2.) PLEASE LABEL ALL BREAKERS. 3.) CONDUCTORS TO BREAKERS TO BE SIZED PER AMPACITY ALLOWED BY MANUFACTURE AND TABEL 310-16. |
|
11/27/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*CALL FOR FINAL WHEN CHANGE OVER COMPLETED. | |
11/22/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0935*1.) NO PROGRESS AS OF INSP. ON 11/8/02 2.) A RE INSPECTION FEE IS ASSESED, PLEASE PAY RE INSPECTION FEE 201 N STONE PRIOR. TO FUTURE INSPECTIONS. | |
11/13/2002 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection 0000* | |
11/05/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) SUPPORT RISER CONDUIT WITHIN 3' OF SERVICE ENCLOSURE, MUST USE MIN 1/4" BOLTS. 2.) SUPPORT 2" CONDUIT RUN UNDER PANEL. |