Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/04/2003 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*SENT TO TEP ON 2/5/03 AT 9:15AM OK TO CLEAR. | |
| 01/30/2003 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0215* CORRECTION REQUIRED: 1.) A NEW GROUNDING SYSTEM IS REQUIRED FOR ALL NEW SERVICE EQUIPMENT. THE EXISTING GROUND IS CONSIDERED "UNPROVEN". SEE DIAGRAM BELOW FOR TYPICAL GROUNDING SYSTEM. NEC ART. 250. 2.) THE CIRCUIT BREAKER BOX AT THE HOUSE IS LOCATED TO HIGH ABOVE GROUND LEVEL. THE ELECT. CODE REQUIRES THAT CIRCUIT BREAKERS BE LOCATED NOT HIGHER THAN 6FT.7" ABOVE GROUND LEVEL. NEC ART 380-8. PLEASE CORRECT AND RECALL INSPECTION. |