Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 01/28/2003 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR 1.) PER CHUCK DELEON. OF TEP. CLEARANCE OVER SHED ROOF ARE ACCEPTABLE. |
| 10/30/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) A PERMANENT METAL ADDRESS LABEL IS NEEDED 2.) USE APPROVED BREAKERS AS LISTED BY MANUFACTURE ON THE LABELS. 3.) PLEASE LABEL 4.) FILL ALL UNUSED OPENINGS IN JUNCTION BOX. 5.) PLEASE IDENTIFY NEUTRAL CLOSER TO WETHER HEAD. 6.) MAINTAIN CLEARENCES ABOVE SHED ROOF. |