Permit: T02EL02125

Parcel: 129120240


Addresses:

1020 E 26TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
11/14/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR UPGRADE.
11/06/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) THE #4 COPPER GROUND WIRES AT BOTTOM OF 3/4" EMT NEED TO BOND TO END OF CONDUIT. 2.) THE ADDRESS MUST BE OF A PERMANENT TYPE.
3.) VERIFICATION OF ALL #12 CIRCUITS INSIDE NOT DONE.
11/01/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) SLEEVE FOR GROUNDING ELECTRODE CONDUCTOR REQUIRE BONDING FROM CONDUIT TO EACH WIRE ALSO REQUIRE A GROUNDING BUSHING ON TOP. OR REPLACE WITH PVC CONDUIT. 2.) MUST CHECK TO SEE IF ALL OF HOUSE IS IN FACT WIRED WITH #12 WIRE. 3.) MUST HAVE PERMANENT ADDRESS TAG 4.) OK TO BURRY GROUND WIRE PLEASE CORRECT AND RECALL.