Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/17/2002 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*SENT TO TEP ON 12/18/02 AT 9:15AM OK TO CLEAR TEMP SERVICE OK CABLE DROP. CALL FOR FINAL AFTER TIE IN OF NEW SERVICE. | |
| 12/10/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*NOTES 1.) GROUND ELECTRODE CONDUCTOR TO BE CONTINUEOUS WITHOUT A SPLICE, 250-50 NEC. 2.) NEED TO VERIFY WATER & GAS BOND RUN BACK TO SERVICE ENCLOSURE, IF RUN IN METAL CONDUIT YOU MUST INSTALL BOND BUSHINGS AND BOND TO GROUND BONDING WIRE. 3.) NEED TO INSPECT WIRING THRU WALL TO INTERIOR OF SOUTH ROOM. 4.) A RE-INSPECTION FEE WILL BE ASSESSED IF NOT READY. |
|
| 11/14/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*1.) BRASS GROUND CLAMPS TO HAVE BRASS SCREWS, 2.) #4 GROUNDING CONDUCTOR NOT CLAMPED PROPERLY ON CLAMP, SHOULD TERMINATED ON HOLE DESIGNED FOR TERM. 3.) ADDRESS LABEL TO BE SCREWED OR RIVITED TO ENCLOSURE, STICK ON #'S NOT APPROVED. 4.) SUPPORT PVC CONDUIT. 5.) NEED TO VERIFY WATER & GAS BONDING. |
|
| 11/13/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0215* |