Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL02109
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/26/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*1.) NOTES 1.) INSTALL (2) GROUND RODS MIN 6' APART. PER 250 NEC. 2.) TRY TO ARRANGE WIRING IN PANEL NEATER TO ACCOMADATE INSTALLATION OF DEADFRONT. WIRING PUSHING AGAINST DEADFRONT. |