Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/04/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 11/5/02 AT 9:15AM OK SERVICE UP GRADE ENEGIZE #3 ONLY AS PER TEP. |
| 11/01/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) IF A BACKFEED BREAKER IS USED, USE AN APPROVED HOLD DOWN DEVICE 384-16. 2.) CORRECTLY FILLUNSED OPENING IN SUBPANEL 3.) LABEL BREAKER 4.) SECURE CONDUCTOR TO BOX 373-5. |
| 10/30/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) WE HAVE MULTIPOLE TERMANATIONS AT LUG ON NEUTRAL BAR 110-14. 2.) PLEASE CLEAN SURFACES UNDER LUG AND GROUND BAR 250-12. 3.) WHERE IS NEUTRAL BAR. GROUND BAR IS BEING USED FOR NEUTRALS 4.) PLEASE PROTECT CONDUCTORS FROM SHARP METAL EDGES IN TOP OF METER PACK. 5.) PLEASE VERIFY GAS BONDING FOR EACH UNIT. 6.) ACCESS TO INSPECT INTERIOR TERMANATION WILL NEED TO BE PROVIDED 7.) SUPPORT CONDUIT ON ROOF AT UNIT #1. |