Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 11/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 11/06/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0215*1.) REMOVE THE CHASE NIPPLE CONNECTING THE LB TO THE PANEL AND REPLACE WITH A SHORT THREADED NIPPLE. USE LOCKNUTS ON BOTH SIDES AND A GROUNDING BUSHING TO BOND THE EMT TO THE MAIN GROUND BAR. 2.)THE GROUNDING WIRE IS ON THE WRONG SIDE OF THE CLAMP AT THE GROUND RODS. SEE DRAWING BELOW. 3.) TERMINATE YOUR WIRING TO CIRCUIT BREAKERS IN PANEL. IDENTIFY & MARK PANEL. 4.) INSTALL ADDRESS NUMBERS BELOW METER . USE METAL EMBOSSED STRIP OR METALLIC STICK ON NUMBERS DO NOT USE MAGIC MARKER", PENCIL OR PEN. |