Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/21/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 10/22/02 AT 9:15AM. OK TO CLEAR |
| 10/17/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0210*1.) CORRECTION REQUIRED 1.) DRIVE GROUND RODS TO 2" BELOW EARTH GRADE 2.) PER NEC TABLE 310--15, A 200 MP. SERVICE REQUIRES MINIMUM 2/0 SERVICE CONDUCTORS (COPPER). THEY MUST HAVE INSULATION WHICH IS MARKED "SUNLIGHT RESISTANT." LEAVE SAMPLE PIECE WITH MARKINGS FOR INSPECTIONS. 3.) MARK CIRCUIT DIRECTORY ON PANEL. INDICATE WHAT AREAS OF HOUSE EACH CIRCUIT BREAKER SERVES. 4.) WIRE BRUSH GAS AND WATER PIPES CLEAN WHERE GROUND CLAMPS ARE ATTACHED. |