Permit: T02EL02061

Parcel: 135081070

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
10/21/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 10/22/02 AT 9:15AM. OK TO CLEAR
10/17/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0210*1.) CORRECTION REQUIRED 1.) DRIVE GROUND RODS TO 2" BELOW EARTH GRADE 2.) PER NEC TABLE 310--15, A 200 MP. SERVICE REQUIRES MINIMUM 2/0 SERVICE CONDUCTORS (COPPER). THEY MUST HAVE INSULATION WHICH IS MARKED "SUNLIGHT RESISTANT." LEAVE SAMPLE PIECE WITH MARKINGS FOR INSPECTIONS. 3.) MARK CIRCUIT DIRECTORY ON PANEL. INDICATE WHAT AREAS OF HOUSE EACH CIRCUIT BREAKER SERVES. 4.) WIRE BRUSH GAS AND WATER PIPES CLEAN WHERE GROUND CLAMPS ARE ATTACHED.