Permit: T02EL02050

Parcel: 115043860


Addresses:

1147 N 1ST AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/08/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
10/21/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) SUPPORT RISER USING LISTED AND APPROVED HARDWARE USE 1/4" MIN BOLTS. 1/2" FLEX CONNECTOR USED AS A SPACER NOT APPROVED ON RISER CONDUIT. 2.) COLOR CODE GROUNDED CONDUCTOR OR NEUTRAL WHITE, NOT GREEN. 3.) SUPPORT W/P BOX FOR GFI RECEPT, USE PROPER APPROVED NIPPLE FOR CONNECTION, NOT A ROMEX CONN. 4.) BOND GAS PIPING. 5.) SUPPORT #4 BARE GROUND TO WALL OF HOUSE.