Permit: T02EL02043

Parcel: 11519010B


Addresses:

1787 W RILLITO DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/12/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR SENT TO TEP ON 12/13/02 AT 9:15AM WHEN IDENTIFYING CONDUCTORS, TAPE SHOULD CONDUCTOR PLEASE IDENTIFY DISCONNECT ENDS ALSO AS DISCUSSED.
12/11/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) METAL GROUNDING ELECTRODE RACEWAY TO BE BONDED BOTH ENDS PER CODE 250-64 (E)
3.) CONDUCTOR TO BE COLOR CODED PER 210-5 AND CITY AMENDMENTS.
4.) BONDING DEVICE NEEDED BOTH SIDES OF NIPPLE 250-94.
5.) ANTI OXIDE COMPOUND NEEDED FOR AL CONDUCTORS.
6.) PLEASE POST A PERMANENT ADDRESS FOR PROPERTY.
12/09/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0945*
CAN NOT LOCATE SERVICE ADDRESS NOT POSTED ON BUILDINGS OR METERS.