Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/12/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000*OK TO CLEAR SENT TO TEP ON 12/13/02 AT 9:15AM WHEN IDENTIFYING CONDUCTORS, TAPE SHOULD CONDUCTOR PLEASE IDENTIFY DISCONNECT ENDS ALSO AS DISCUSSED. | |
| 12/11/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000*1.) METAL GROUNDING ELECTRODE RACEWAY TO BE BONDED BOTH ENDS PER CODE 250-64 (E) 3.) CONDUCTOR TO BE COLOR CODED PER 210-5 AND CITY AMENDMENTS. 4.) BONDING DEVICE NEEDED BOTH SIDES OF NIPPLE 250-94. 5.) ANTI OXIDE COMPOUND NEEDED FOR AL CONDUCTORS. 6.) PLEASE POST A PERMANENT ADDRESS FOR PROPERTY. |
|
| 12/09/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0945* CAN NOT LOCATE SERVICE ADDRESS NOT POSTED ON BUILDINGS OR METERS. |