Permit: T02EL02037

Parcel: 12203014B


Addresses:

2216 N BELVEDERE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/18/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 11/19/02 AT 9:15AM
11/14/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*
1.) INSTALL BOND BUSHING ON RISER CONDUIT.
2.) BOX WHERE BRANCH CIRCUITS ENTER HOUSE NEEDS TO BE ATTACHED.
3.) 1/4" MIN BOLTS REQUIRED TO SUPPORT RISER.
11/13/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*
1.) SERVICE RISER TO BE BONDED 250-94.
2.) TIGHTEN LOOSE SEALTITE FITTINGS
3.) FILL UNUSED OPENINGS IN PANEL
4.) PLEASE VERIFY WHO IS LICENSED ELECTRICAL CONTRACTOR
5.) RISER STRAP TO BE SECURED TO WALL.