Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/14/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
IVRS - Inspection 0000* |
| 10/11/2002 |
ELECTRIC - INTERMEDIATE |
|
Not ready for Inspection |
IVRS - Inspection 0000* |
| 10/09/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0210*CORRECTION REQUIRED 1.) REPLACE RISER CONDUCTORS (3) WITH 3/0 COPPER THHN SUNLIGHT RESISTANT INSULATION WIRES. 2.) PLACE METALLIC ADDRESS NUMBERS ON THE SERVICE PANEL BELOW THE METER. 3. INSTALL GROUND WIRE, TWO 5/8" X 8' GROUND RODS, AND GROUND TO COLD WATER AND GAS PIPE. USE #4 BARE COPPER WIRE. COMPLETE & RECALL INSPECTION. |