Permit: T02EL02016

Parcel: 107080970


Addresses:

833 W KELSO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/11/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*OK TO CLEAR 1.) GROUNDING ELECTRODE CONDUCTOR TO BE CONDINOUS TO GROUNDED TERMANAL. SPLICES NOT TO BE MECHANICAL. 2.) PLEASE LABEL BREAKERS CORRECTLY. 3.) FITTING TO BE TIGHTENDED AND WEATHER PROOF OUTSIDE. 4.) PLEASE VIERFY 2ND GROUND ROD AND GAS BONDING. 5.) 1/4" MININUM HARDWARE IS NEEDED FOR PANEL TO WALL. 6.) BREAKER TO BE LISTED FOR USE BY 7.) SERVICE FEEDER TO BE SIZED PER CODE 310-15 (B) (6).
10/10/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*