Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 10/10/02A AT 9:15AM OK TO CLEAR OK CABLE DROP. |
| 10/08/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*SEE PREVIOUS INSP. WRITE UP. |
| 10/03/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) AC UNIT WITH APPLIANCE LORD HARD WIRED INTO NEW W/P BOX NOT AN APPROVED WIRING METHOD 110-3, 90-4. 2.) SUPPORT RISER WITHIN 3' OF ENCLOSURE USE 1/4" BOLTS. PER NEC. 3.) SELA SEALTITE FITTING AT TOP OF ENCLOSURE TO PREVENT WATER LEAKAGE.CAN SEE DAYLIGHT THRU LOCKNUT. 4.) PLUG UNUSED OPENING WITH APPROVED W/P SEAL. 5.) CHANGE PERMIT DESCRIPTION TO 100AMP. PER INSTALLATION. |