Inspection Status: Partial Approval
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/30/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR SER UPGRADE. CALL FOR FINAL WHEN COMPLETE. 3046 N MOUNTAIN A & B. 3046 N MOUNTAIN. OK TO CLEAR UPGRADES. |
| 10/28/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) THERE HAS TO BE AN ADDRESS ON EACH METER OR SERVICE IT FEEDS 2.) WHERE IS THE WATER BOND. 3.) THE LB ON TOP OF THE NON RAIN TIGHT GUTTER HAS TO BE IN A POSITION TO OPEN COVER 4.) THE GUTTER YOU ARE ATTEMPING TO REVISE IS A NON RAIN TIGHT OUTSIDE ONCE YOU USE IT, IT HAS TO BE UP GRADED TO RAIN TIGHT. |