Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/08/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*SENT TO TEP ON 10/9/02 AT 9:15 AM. OK TO CLEAR. |
| 10/02/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0218* |
| 10/02/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) SERVICE IS AN EXISTING 100 AMP. OVERHEAD FED. 2.) THE SERVICE EQUIPMENT WAS CHANGED OUT YEARS AGO. 3.) THE SERVICE ENTRANCE CONDUCTORS MUST BE REPLACED WITH #4 COPPER OR # 2 ALUM. W/SUNLIGHT RESISTANT INSULATION. LEAVE SAMPLE OF WIRES WITH LEGIBLE MARKINGS FOR VERIFICATION. 4.) INSTALL SEALABLE SCREW ON PANEL COVER BELOW METER. |