Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02EL01913
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/08/2002 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
09/24/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*REMOVE DOUBLE LUGGING AT SINGLE POLE 20 AMP CIRCUIT BREAKER. INSTALL 3/4" LOCKNUT ON 3/4" CONDUIT TO ASSURE GROUNDING PATH. MECHANICAL CONTRACTOR TO GET PERMIT FOR NEW WORK BEING DONE. |