Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/22/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 10/16/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0215*1.) COPPER AND ALUMINUM CANNOT BE SPLICED DIRECTLY TOGETHER. USE A TWO COMPARTMENT LUG OR BUTT SPLICE RATED CU/AL. 2.) THE NEUTRAL CANNOT BE LESS THAN #8. CHANGE OUT FROM PANEL TO J-BOX.THANKS. |
| 09/23/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) THE GREEN WIRES IN THE JUNCTION BOX TO THE EAST OF THE NEW SERVICE ARE NEUTRALS AND NEED TO BE TAPED WHITE. 2.) THE PVC BELOW SERVICE AND AT RAMADA NEEDS TO BE SCH 80. CALL FOR FINAL WHEN CHANGE OVER COMPLETED. |