Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/16/2002 |
ELECTRIC - FINAL |
|
Approved |
APPROVED OK TO CLEAR SERVICE INC. & RECONN. |
| 10/14/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*SENT TO TEP ON 10/15/02 AT 9:15AM. |
| 10/11/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*NEED TO DETERMINE DIFFERENCE BETWEEN CLASSFIELD AND LISTED FOR CIRCUIT BREAKERS. 2.) WHAT ARE UNUSED BREAKERS FOR ? |
| 09/30/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) PLEASE USE AN APPROVED FITTING TO CONNECT TO LB.S CHASE NIPPLE NOT APPROVED. 2.) USE BREAKERS APPROVED FOR USE BY MANUFACTURE 3.) PLEASE SUPPORT RISER WITHIN 2' OF HUB 4.) GAS BOND TO BE CONNECTED TO INTERIOR PIPING. 5.) PLEASE CONNECT WATER BOND TO OTHER SIDE OF VALVES REGULATOR, AND UNIONS |