Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 09/18/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) USE LISTED FITTING TO PENETRATE WEATHER PROOF J-BOX INTO PANEL 2.) USE SEALING LOCKNUTS FOR PENETRATIONS ABOVE BREAKER AREA. 3.) SUPPORT RISER WITHIN 3' OF METER ENCLOSER,USE MIN 1/4" BOLTS. |