Permit: T02EL01815

Parcel: 130102480


Addresses:

3166 E 28TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/14/2003 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 1/15/03 AT 9:15AM PLEASE CLEAR FINAL.
12/09/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0215*1.) 4 X 4 X 4 J BOX IS CRAMMED WITH SPLICES SUBMIT CALCULATION TO JUSTIFY ITS USE OR REPLACE IT WITH A LARGER J-BOX
2.) CHASE NIPPLES ARE NOT ALLOWED FOR TERMINATION.
TO THE PANEL. USE A SHORT THREADED NIPPLE & LOCKNUTS.
3.) COMPLETE THE CIRCUIT DIRECTORY/INDEX.
4.) EXPOSE THE GROUND ROD ENDS FOR INSPECTION.
5.) ADD CLAMPS TO SUPPORT GORUND WIRE & FASTEN TO WALL.