Permit: T02EL01813

Parcel: 121091350

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/16/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
09/12/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES SELF TAPPING SHEET METAL SCREWS NOT ALLOWED TO ATTACH GROUND LUGS. SEE ARTS 250-8,250 146 148. 370 40 D 99NEC. OK TO BACKFILL TRENCH.
09/06/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*OK CABLE DRO OK TO CLEAR TEMP POWER 1.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, NO MARKING PEN. 2.) GROUND J-BOX AT HOUSE. 3.) RECALL INSPECTION FOR FINAL WHEN HOUSE & SHOP TIED IN TO NEW SERVICE.