Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T02EL01800
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/26/2003 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection 0000* | |
| 02/25/2003 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*THE SPLICES YOU MADE IN THE METAL BOX UNDER THE YELLOW WIRE NUTS CANNOT BE SHOWING COPPER. THIS IS DANGEROUS IN A METAL BOX. REDO SPLICES TO WHERE ALL COPPER WIRE IS IN WIRE NUTS. LEFT BOX OPEN FOR YOU TO SEE. |
|
| 02/24/2003 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*#2 ABOVE HAS NOT BEEN FIXED ELECTRICAL WIRING (ROMEX) CANNOT BE RUN IN EXPOSED CONDUCTORS. | |
| 02/18/2003 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0245*/ 1) THE WATER HEATER IS TO SMALL FOR THE RESIDENCE. IF ELECTRIC IT MUST BE PERMANENTLY WIRED WITH A DEDICATED CIRCUIT 2) FIX SPLICES IN CLOSET ATTIC SPACE. REPLACE WITH COMPLETE CABLE RUNS OR ADD JUNCTION BOXES | |
| 09/05/2002 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection 0999*1.) AN APPROVED LIGHT FIXTURE FOR LIVING ROOM IS NEEDED. 2.) WE HAVE GROUNDED RECEPTICALS ON AN UNDERGROUND SYSTEM 3.) PROVIDE AN APPROVED EXTENDER RING WHERE MORE THAN 1/8" EXPOSED TO COMBUSTABLES. 4.) PLEASE USE FUSES RATED FOR CONDUCTOR AMPACITY. 5.) SMOKE DETECTORS ARE NEEDED. 6.) A LIGHT AND SWITCH ARE NEEDED FOR BACK PORCH. 7.) PLEASE USE AN APPROVED WIRING METHOD FOR COOLER. 8.) A LICENSED ELECTRICAL CONTRACTOR TO MARE REPAIRS. |