Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/18/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 09/09/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) USE MIN. 1/4" BOLTS TO SUPPORT RISER, ALSO SEE TEP SPECS. 910-4 NEC. 110-12.NEC. 2.) GROUNDING ELECTRODE CONDUCTOR TO MIN #6. PER ART 250-66. NEC. 3.) I.D. CIRCUIT BREAKER TO DWELLING AS TO LOADED SERVED, NOT JUST EXISTING. |