Permit: T02EL01770

Parcel: 122170200


Addresses:

3461 E CODY ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/18/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP.
09/09/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) USE MIN. 1/4" BOLTS TO SUPPORT RISER, ALSO SEE TEP SPECS. 910-4 NEC. 110-12.NEC. 2.) GROUNDING ELECTRODE CONDUCTOR TO MIN #6. PER ART 250-66. NEC. 3.) I.D. CIRCUIT BREAKER TO DWELLING AS TO LOADED SERVED, NOT JUST EXISTING.