Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/13/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 09/09/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*THE GROUNDING ELECTRODE CONDUCTOR SHALL BE CONNECTED TO THE GROUNDED SERVICE CONDUCTOR 250-24 NEC. 250-24-4 250-28. 2.) THE BOND BUSHING INSIDE THE LOAD CENTER TO BE BONDED TO ENCLOSURE 250-94NEC. |
| 08/29/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) USE MIN 1/4" BOLTS TO SUPPORT RISER CONDUIT #10 SHEET METAL SCREWED TO WOOD SIDING NOT STRONG ENOUGH. 110-3,110-12. NEC. ALSO SEE TEP SPEC'S. 2.) GROUND 6 X6X4 J-BOX 250-146-148. 370-40D NEC. 3.) NEUTRAL OR GROUNDED CONDUCTOR TO BONDED AT ONE LOCATION ONLY ON CUSTOMER SIDE OF METER. 250-24A, 250-142. SHOULD BE AT THE MAIN DISCONNECTING MEANS ONLY. |