Permit: T02EL01762

Parcel: 122163050


Addresses:

3841 E EDISON PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
12/12/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*.
1) NOTE: HOMEOWNER TO CORRECTLY IDENTIFY PANEL DIRECTORY
10/22/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*
1. BOND GAS PIPE TO SERVICE
2. EXPOSE GROUND RODS OR DRIVE NEW ONES
3. PROPERLY IDENTIFY PANEL DIRECTORY
4. RACEWAYS INTO SERVICE TO BE RAIN TIGHT
5. 60 AMP BREAKER TO SUB-PANEL IS CRACKED