Permit: T02EL01761

Parcel: 127060610

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
09/30/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*SENT TO TEP ON 10/1/02 AT 9:15 AM.
09/24/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*CONTR INSTALLED NEW 200A ALL IN ONE WITH NEW RISER ETC. 1.) SUPPORT RISER WITH 1/4" BOLTS, PLASTIC ANCHOR WITH #10 SCREW NOT SUFFICIANT. ALSO DRYWALL SCREWS NOT ACCEPTABLE. 2.) INSTALL 2 GROUND RODS 6' MIN APART 3.) INSTALL BUSHED CONNECTOR WHERE CABLE EXISTS CONDUIT SLEEVE. 4.) UNISTRUT SUPPORT FOR 3/4" CONDUITS PULLING OUT OF WALL. 5.) BOND GAS PIPING. 6.) NO ADDRESS LABEL.
08/30/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*SEE CORRECTION LIST OF 8-29-02 INSPECTION.
08/29/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*