Permit: T02EL01761

Parcel: 127060610

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
09/30/2002 ELECTRIC - INTERMEDIATE Approved
08/29/2002 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection 0245*1.) DISCONNECT SWITCH, GUTTER, NOT RATED FOR OUTDOOR USE. USE NEMA 3R. 2.) CONDUCTOR SIZE TO SMALL FOR 200AMP. SERVICE FROM GUTTER TO MAIN BREAKER PANEL. SHOULD BE 3/0 CU. 3.) CLEARANCE FOR POWER WILL BE SUBJECT TO TEP APPROVAL OF METER LOCATION, TOO HIGH 4.) TOP PENETRATIONS TO BE SEALED WITH PROPER HARDWARE/FITTING TO BE RAINTITE.