Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date |
Description |
Inspector |
Results |
Comments |
| 09/30/2002 |
ELECTRIC - INTERMEDIATE |
|
Approved |
|
| 08/29/2002 |
ELECTRIC - INTERMEDIATE |
|
Denied |
IVRS - Inspection 0245*1.) DISCONNECT SWITCH, GUTTER, NOT RATED FOR OUTDOOR USE. USE NEMA 3R. 2.) CONDUCTOR SIZE TO SMALL FOR 200AMP. SERVICE FROM GUTTER TO MAIN BREAKER PANEL. SHOULD BE 3/0 CU. 3.) CLEARANCE FOR POWER WILL BE SUBJECT TO TEP APPROVAL OF METER LOCATION, TOO HIGH 4.) TOP PENETRATIONS TO BE SEALED WITH PROPER HARDWARE/FITTING TO BE RAINTITE. |