Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/22/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*/ 1) DISCONNECT FURNACE CIRCUIT AT MAIN PANEL UNTIL REPAIRS ON FURNACE ARE COMPLETED 2) EACH BEDROOM MUST HAVE A SMOKE DETECTOR 3) REMOVE KEYED DEAD BOLTS AND REPLACE WITH TURN HANDLE LOCKS |