Permit: T02EL01712

Parcel: 113044030


Addresses:

1028 E HALCYON RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/28/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/26/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*1.) RISER CONDUIT LOOSE USE MIN 1/4" ANCHOR BOLTS TO SUPPORT. 2.) NO COMPLIANCE WITH ITEM #3 LAST INSPECTION WRITE UP ALSO #5,#6. 3.) NO ANSWER AT DOOR..
08/23/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*1.)GROUND RODS TO BE DRIVEN 1ST,45 2ND, INTRENCH 3RD IF THE FIRST 2 CAN NOT BE MET. 2.) A PERMNENT METAL ADDRESS LABEL IS NEEDED. 3.) A BONDING DEVICE IS NEEDED ON RISER. 4.) LABEL ALL BREAKERS 5.) OLD PANEL NOT LISTED AS JUNCTION BOX 6.) PLEASE PROVIDE ACCESS TO JUNCTION BOX FOR NEW NM CABLES.
08/22/2002 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection 0000*