Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/28/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* |
| 08/26/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245*1.) RISER CONDUIT LOOSE USE MIN 1/4" ANCHOR BOLTS TO SUPPORT. 2.) NO COMPLIANCE WITH ITEM #3 LAST INSPECTION WRITE UP ALSO #5,#6. 3.) NO ANSWER AT DOOR.. |
| 08/23/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.)GROUND RODS TO BE DRIVEN 1ST,45 2ND, INTRENCH 3RD IF THE FIRST 2 CAN NOT BE MET. 2.) A PERMNENT METAL ADDRESS LABEL IS NEEDED. 3.) A BONDING DEVICE IS NEEDED ON RISER. 4.) LABEL ALL BREAKERS 5.) OLD PANEL NOT LISTED AS JUNCTION BOX 6.) PLEASE PROVIDE ACCESS TO JUNCTION BOX FOR NEW NM CABLES. |
| 08/22/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000* |