Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/20/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR 2137 & 2139. OK CABLE DROP. |
| 08/19/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) GAS PIPE BONDING TO BE ON CUSTOMER SIDE OF GAS METER. 250-104 NEC. 2.) SPLIT BOLT NOT ALLOWED FOR GROUNDING ELECTRODE BOND JUMPER BETWEEN SERVICES, MUST BE IRREVERSIBLE TYPE SPLICE, EITHER CRIMP OR EXOTHERMIC WELD. |