Permit: T02EL01693

Parcel: 107010460

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/20/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*OK TO CLEAR.
08/19/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*1.) PLEASE USE 1/4" MININUM HARDWARE TO SUPPORT RISER NOT CABINET SCREWS ALSO PANEL TO POLE. 2.) SUPPORT/STRAP GROUNDING ELECTRODE CONDUCTOR TO POLE 3.) BREAKER TO BE LABELED. 4.) PLEASE IDENTIFY NEUTRAL CLOSER TO WETHER HEAD. 5.) FINISH INSTALLING METER FACE COVER.