Permit: T02EL01688

Parcel: 134113020


Addresses:

8116 E BEVERLY ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL01688

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
10/02/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
09/26/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*OK TO CLEAR SER INC. FINISH BRANCH CIRCUITS AND SCHEDULE FINAL INSP.
09/25/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*TAKE SCEWS OUT OF HUB CONNECTION AND TRY THREADING IT ONTO OFFSET. NIPPLE THIS WAY. IF THIS DOESNT WORK INSTALL A LOCKNUT BETWEEN HUB & OFFSET NIPPLE TO ASSURE ADEQUATE BONDING 954-0161 IF YOU HAVE ANY QUESTIONS.
09/24/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) OFFSET NIPPLE NEEDS TO BE WRENCH TIGHT INTO THE 2" HUB. 2.) USE ANTI OXIDATION PASTE ON ALL ALUM. TERMINATIONS. 3.) CLEAN PAINT OFF OF WATER LINE WHERE WATER BOND CLAMP ATTACHED. 4.) CLEAN PAINT OFF OF GAS LINE WHERE GAS BOND CLAMP ATTACHED.