Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 10/02/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 09/26/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000*OK TO CLEAR SER INC. FINISH BRANCH CIRCUITS AND SCHEDULE FINAL INSP. |
| 09/25/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*TAKE SCEWS OUT OF HUB CONNECTION AND TRY THREADING IT ONTO OFFSET. NIPPLE THIS WAY. IF THIS DOESNT WORK INSTALL A LOCKNUT BETWEEN HUB & OFFSET NIPPLE TO ASSURE ADEQUATE BONDING 954-0161 IF YOU HAVE ANY QUESTIONS. |