Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL01688
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2002 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
| 09/26/2002 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection 0000*OK TO CLEAR SER INC. FINISH BRANCH CIRCUITS AND SCHEDULE FINAL INSP. | |
| 09/25/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*TAKE SCEWS OUT OF HUB CONNECTION AND TRY THREADING IT ONTO OFFSET. NIPPLE THIS WAY. IF THIS DOESNT WORK INSTALL A LOCKNUT BETWEEN HUB & OFFSET NIPPLE TO ASSURE ADEQUATE BONDING 954-0161 IF YOU HAVE ANY QUESTIONS. | |
| 09/24/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1.) OFFSET NIPPLE NEEDS TO BE WRENCH TIGHT INTO THE 2" HUB. 2.) USE ANTI OXIDATION PASTE ON ALL ALUM. TERMINATIONS. 3.) CLEAN PAINT OFF OF WATER LINE WHERE WATER BOND CLAMP ATTACHED. 4.) CLEAN PAINT OFF OF GAS LINE WHERE GAS BOND CLAMP ATTACHED. |