Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 09/09/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 08/20/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*1.) MAINTAIN WORKING CLEARENCE ABOUT PANEL. 2.) A SEALING DEVICE IS NEEDED FOR ALL FITTING ENTERING ABOVE BUSS. 3.) TIGHTEN PVC FITTING 4.) PROVIDE A BOND JUMPER AROUND ELECTRIC UNION. 5.) GROUNDING EQUIPMENT CONDUCTORS TO BE TREMANATED AS PER MANUFACTURE. 6.) WE HAVE MULTIPOLE TERMANATIONS AT LUGS IN GUTTER. |
| 08/16/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*PLEASE PROVIDE ACCESS TO BACKYARD GATES LOCKED. |