Permit: T02EL01673

Parcel: 112041670

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/22/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*/ 1) OK TO CLEAR SERVICE INCREASE
08/21/2002 ELECTRIC - FINAL Partial Approval IVRS - Inspection 0000*/ 1) NOTES: INSTALL NEUTRAL BOND JUMPER TO NEUTRAL BAR AT SUB-PANEL, PER 250-32 (B-2)
08/16/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0245*NOTES 1.) SERVICE EQUIP TO HAVE 36" DEDICATED WORKING CLEARANCE IN FRONT OF 110-26 NEC. 2.) SEPERATE STRUCTURE TO HAVE OWN GROUNDING ELECTRODE SYSTEM. PER 250-32,52 NEC. 3.) ALL CIRCUIT BREAKERS TO BE I.D.