Permit: T02EL01672

Parcel: 121111400


Addresses:

4754 E LEE ST


Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Permit Number - T02EL01672

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
08/19/2002 ELECTRIC - RECONNECT Denied IVRS - Inspection 0930*1.) INSTALL PERMANENT ADDRESS LABEL ON SERVICE. 2.) LOAD CONDUCTOR NOT ALLOWED TO PASS THRU METER SECTION OF ENCLOSURE PER 230.7 N.EC. 3.) OWNER TO OBTAIN SITE PLAN SUBMIT AT PLANNING & PERMIT 201 N. STONE OBTAIN PROPER PERMIT FOR ELECTRICAL MODIFICATIONS TO STURCTURE 2HR PERMIT PLEASE ALLOW CREDIT OF RECONNECT PERMIT.