Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2002 |
ELECTRIC - CABLE DROP |
|
Approved |
IVRS - Inspection 0000* |
| 09/06/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0920* |
| 08/20/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215*1.) GROUND WIRE MUST BE RUN UNSPLICED. 2.) ATTACH TO HOUSE SIDE OF GAS & WATER PIPES. STEEL BRUSH CLEAN. QUESTIONS CALL AT 909-5147. REFEE WILL BE DUE & PAYABLE BEFORE 4TH INSPECTION. |
| 08/19/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215*1.) GROUNDING IS INCORRECT. ATTACH GROUND WIRE. TO COPPER PIPE SECTION NEAR WHERE IT ENTERS THE HOUSE. THIS APPLIES TO BOTH GAS AND WATER. 2.) EXPOSE AND FLAG THE GROUND RODS ENDS SO CLAMP AND WIRE ARE VISIBLE. 3.) INSTALL 2 PIECE UNISTRUT CLAMP TO RISER PIPE. #1 OF 1ST CORRECTIONS. |
| 08/15/2002 |
ELECTRIC - CABLE DROP |
|
Denied |
IVRS - Inspection 0215*CORRECTION 1.) INSTALL 2 PIECE UNISTRUT CLAMP ON RISER PIPE. ATTACH TO UNISTRUT. 2.) FILL IN CIRCUIT INDEX DIRECTORY. 3.) PUT ADDRESS ON PANEL (BELOW METER SOCKET). USE METALLIC NUMBERS OR EMBOSSED METAL STRIP. DO NOT USE PENCIL, PEN OR "MAGIC MARKER." 4.) COMPLETE THE GROUNDING CIRCUIT PER DIAGRAM BELOW. 5.) TEP MAY REQUIRE BRACE FOR RISER AT ROOF. |