Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 08/29/2002 |
ELECTRIC - RECONNECT |
|
Approved |
IVRS - Inspection 0000*TALKED W/MR GARY ROBERTA OF LONG REALTY HAD QUESTION AND WANTS TO RESCHEDULE HE ASKED ME TO TALK TO DEMISSE TO FIND OUT WHEN IS THE ELECTRICAL CONTRACTOR. |
| 08/16/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999*PLEASE PROVIDE A FLOOR PLAN DELINEATING THE DIFFERENT OCCUPANCIER AND ADDRESS/UNIT NUMBER PERMANENTLY MARK ALL METER (4) WITH PROPER ADDRESS USE METALIC TAG OR UNGRAVED TAGS, REIVETTED TO ENCLOSURE PLEASE HAVE A LICENSED ELECTRICAL CONTRACTOR REPLACE HAVE A LICENSED ELECTRICAL CONTRACTOR REPLACE WIRE IN SERVICE RISER WIREWAY THESE WIRES ARE DETERIORATE AND DANGEROUS. CONDUIT FOR FLOOD NOT SUPPROTED PROPERLY. WIRING TO CATERING TRACK MUST BE COMPLETEY REMOVED. NOV PERMITTED OR INSPECTED WILL NEED A SEPARATE PERMIT AND INSPECTION. |
| 08/15/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0999* |