Permit: T02EL01651

Parcel: 119221870

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/28/2002 ELECTRIC - FINAL Approved IVRS - Inspection 0000*
08/21/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*WILL NEED A GROUNDING ELECTRODE SYSTEM INSTALLED. SUCH AS 2 GROUND RODS, 6 FEET APART. INSTALL A GAS BOND. ROMEX INTO NEW PANEL MUST BE INSTALLED IN RACEWAY UP TO AT LEAST 8FT. ABOVE FINISHED FLOOR. NOTE: POWER COMPANY T.E.P. HAS REQUIRED A 2" HEAVY WALL CONDUIT AS A RISER FOR THE SUPPORT OF THEIR WIRE.