Permit: T02EL01645

Parcel: 113110440


Addresses:

1638 E EDISON ST


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL01645

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
08/16/2002 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*
08/14/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) PLEASE LABEL PANEL WITH A PERMANENT METAL ADDRESS LABEL. 2.) BREAKER NEED TO BE LABELED. 3.) SUPPORT CONDUIT BELOW PANEL AND TIGHTEN FITTINGS. 4.) A GAS BOND IS REQUIRED. 5.) MANUFACTURE STATES NO LOAD CONDUCTORS THROUGH TOP ENDWALL. 6.) FILL ALL UNUSED OPENINGS IN BOXES. 7.) WE HAVE CONDUCTORS CLEARENCE IN IN RUN TO BACK BUILDING TYPE CONDUCTORS SHOW DETERORATION. 8.) PLEASE VERIFY PERMIT FOR NEW A/C INSTALLATION. 9.) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR.