Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL01645
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/20/2002 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000* | |
08/16/2002 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection 0000* | |
08/14/2002 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0999*1.) PLEASE LABEL PANEL WITH A PERMANENT METAL ADDRESS LABEL. 2.) BREAKER NEED TO BE LABELED. 3.) SUPPORT CONDUIT BELOW PANEL AND TIGHTEN FITTINGS. 4.) A GAS BOND IS REQUIRED. 5.) MANUFACTURE STATES NO LOAD CONDUCTORS THROUGH TOP ENDWALL. 6.) FILL ALL UNUSED OPENINGS IN BOXES. 7.) WE HAVE CONDUCTORS CLEARENCE IN IN RUN TO BACK BUILDING TYPE CONDUCTORS SHOW DETERORATION. 8.) PLEASE VERIFY PERMIT FOR NEW A/C INSTALLATION. 9.) PLEASE VERIFY LICENSED ELECTRICAL CONTRACTOR. |