Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/13/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR OK CABLE DROP. |
| 08/12/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0245*1.) GROUND RODS MUST BE FLUSH WITH GROUND LEVEL. 2.)PERMANENT ADDRESS LABEL REQUIRED, NO MARKER PEN. MUST BE SCREWED OR RIVETED. TO ENCLOSURE. 3.) USE PROPER LISTED FITTINGS TO TERMINATE SLB AT BOTTOM OF PANEL. 4.) SECURE #4 BARE GROUND TO WLAL. 5.) SERVICE EQUIP. MUST HAVE 30' HORIZONTAL AND 36" IN FRONT OF CLEARANCE FOR WORKING SPACE. |