Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
Permit Number - T02EL01606
Inspection Description - ELECTRIC - SERVICE UPGRADE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/23/2003 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection 0000*/ 1) OK TO CLEAR INCREASE | |
| 05/02/2003 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection 0245*SERVICE LOCATION IN VIOLATION OF WORKING CLEARANCE DUE TO IRRIGATION SYSTEM PLUMBING, AND SHORT WALL BUILT AROUND SERVICE EQUIP. MUST HAVE 30" HORIZONTAL AND 36" IN FRONT PER 110-26 NEC. 2.) FRONT COVER DOES NOT OPEN ENOUGH TO REMOVE DEAD FRONT COVER SAFELY. |