Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date |
Description |
Inspector |
Results |
Comments |
| 08/19/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Approved |
IVRS - Inspection 0000* |
| 08/12/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Not ready for Inspection |
IVRS - Inspection 0000*1.) ALL FIXTURES ABOVE BUSS. |
| 08/08/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Partial Approval |
IVRS - Inspection 0000* |
| 08/06/2002 |
ELECTRIC - SERVICE UPGRADE |
|
Denied |
IVRS - Inspection 0999*1.) ALL ENTRANCES ABOVE BUSS ARE REQUIRED A SEALING DEVICE OR FITTING. 2.) PLEASE TIGHTEN LOOSE FITTINGS AND LOCK NUTS. 3.) BOND JUNCTION BOX ENCLOUSER 4.) PLEASE BOND BOTH SIDES OF GAS UNION TO MAINTAIN CONTINOSITY. 5.) STRAP AND SUPPORT CONDUIT AS PER CODE. 6.) PROPER HARDWARE IS NEEDED TO SECURE PANEL TO STRUCTURE 1/4" MININUM NOT DRYWALL SCREWS. |