Permit: T02EL01590

Parcel: 10713221A


Addresses:

255 E JACINTO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/19/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
08/12/2002 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*1.) ALL FIXTURES ABOVE BUSS.
08/08/2002 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection 0000*
08/06/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) ALL ENTRANCES ABOVE BUSS ARE REQUIRED A SEALING DEVICE OR FITTING. 2.) PLEASE TIGHTEN LOOSE FITTINGS AND LOCK NUTS. 3.) BOND JUNCTION BOX ENCLOUSER 4.) PLEASE BOND BOTH SIDES OF GAS UNION TO MAINTAIN CONTINOSITY. 5.) STRAP AND SUPPORT CONDUIT AS PER CODE. 6.) PROPER HARDWARE IS NEEDED TO SECURE PANEL TO STRUCTURE 1/4" MININUM NOT DRYWALL SCREWS.