Permit: T02EL01571

Parcel: 124091220


Addresses:

1636 E 10TH ST #01


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T02EL01571

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
08/20/2002 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection 0000*
08/16/2002 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection 0000*MEET WITH CONTACTOR REPRESSITIVE AND WENT OVER JOB.
08/12/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*1.) PERMANENT METAL ADDRESS LABEL ARE NEEDED 2.) MAUFACTURES HOLD DOWN DEVICES ARE REQUIRED ON MAIN BREAKERS 3.) SHEET METAL SCREWS CAN NOT BE USED FOR BONDING 250-8. 4.) PLEASE CLEAN UNDER LUG 250-12. 5.) PLEAE COMPLETE #4,#5,& #8 FOR PREVIOUS INSPECTION.
08/05/2002 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection 0999*THIS IS NOT A SERVICE UPGRADE. IT IS A NEW SERVICE 1.) ADDRESS DO NOT MATCH PERMIT. 2.) PLEASE VERIFY FEEDER CONDUCTORS PASSING THROUGH 1ST BUILDING 3.) PLEASE VERIFY UNDERGROUND INSPECTIONS FOR FEEDER CONDUIT 4.) USE AN APPROVED CONNECTOR FOR SE CABLE AT JUNCTION BOX 5.) BOND JUNCTION BOX ENCLOUSER. 6.) GAS BONDING IS REQUIRED AS PER CODE 1ST & 2ND BUILDING.7.) A MAIN DISCONNECTING MEANS WILL BE NEEDED AT 2ND BUILDING 7.) A MAIN DISCONNECTING MEANS WILL BE NEEDED AT 2ND BUILDING AS PER CODE 225-31, 225-32. 8.) NO LOADS CONNECTED AT THIS TIME PLEASE FINISH PANEL. 9.) PLEASE LABEL PANEL WITH AN ADDRESS OR NUMBER.10.) VERIFY WATER BOND TO MAIN SERVICE.