Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 10/03/2002 |
ELECTRIC - RECONNECT |
|
Approved |
|
| 08/09/2002 |
ELECTRIC - RECONNECT |
|
Denied |
IVRS - Inspection 0333*1.) CORRECT FIXTURE AT FRONT PORCH WIRING CANNOT BE SHOWING 2.) PANEL INSIDE -THE FEEDER FROM SERVICE TO PANEL DOES NOT CONTAIN A GROUND WIRE ITS AN UNGROUNDED SYSTEM THERE FOR THE NEUTRALS AND GROUNDS CANNOT BE COMBINED ALL THE OUTLETS HAVE TO BE A TWO WIRE TYPE WHERE IS COVER TO PANEL 3.) ALL DEVICE COVERS TO BE PUT ON 4.) GAS RANGE WOULD NEED EXHAUST FAN REMOVED 5.) RECEPTACLES ON SIDES ON KITCHEN SINK TO BE GFI TYPE 6.) INSTALL BATTERY TYPE SMOKE DETECTOR SIN ALL BEDROOMS. 7.) THE GROUND WIRE TO SERVICE HAS BE INSTALL A NEW GROUNDING SYSTEM WITH GAS & WATER BONDS. 8.) FEEDER FROM PANEL (SERVICE) TO J-BOX AT PORCH INCORRECT HAS TO BE REINSTALLED CORRECTLY. 9.) CUT ROMEX WIRES BY ABOVE J-BOX I NOT USED REMOVE. 10.) REAR STORAGE ROOM, LOCKED NEED TO BE INSPECTED. SINCE THIS IS A VACANT HOUSE THE STATE REGISTRAT OF CONTRACTOR REQUIRES A C-11 LICENSED ELECTRICAL CONTRACTOR TO MAKE CORRECTION. HAVE HIM OBTAIN A GENERAL REPAIR PERMIT MAKE CORRECTIONS AND RECALL FOR INSPECTION. |