Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL01537
Inspection Description - ELECTRIC - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0999*IMPROPER CLEARANCE IN FRONT OF SERVICE DUE TO CATV PEDESTAL INSTALLED. NO ACCESS TO BACK YARD INSIDE UNITS TO COMPLETE MY INSPECTION A RE-FEE IN DUE BEFORE THE NEXT INSPECTION. | |
08/21/2002 | ELECTRIC - FINAL | Denied | GROUND RODS TO BE 30" HORZONTAL INSTALL MAIN GROUNDING ELECTRODE AT SERVICE NEUTRAL DESIGNATED ON EQUIPMENT PAPERWORK.-CABLE T.V. MUST BE OUT OF DEDICATED WORK SPACE AND REQUIRED CLEARANCE. NEED GROUND BUSH & BOND JUMPER FOR RISER. | |
08/05/2002 | ELECTRIC - FINAL | Partial Approval | 2010 AND 2005 OK CABLE DROP BUT NO CLEARANCE FOR 511 #1, 511.#2. OWNER TO OBTAIN PERMITS FOR INSIDE CONST. PRIOR TO CLEARANCE FOR POWER. |