Permit: T02EL01537

Parcel: 117142090

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T02EL01537

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
08/27/2002 ELECTRIC - FINAL Denied IVRS - Inspection 0999*IMPROPER CLEARANCE IN FRONT OF SERVICE DUE TO CATV PEDESTAL INSTALLED. NO ACCESS TO BACK YARD INSIDE UNITS TO COMPLETE MY INSPECTION A RE-FEE IN DUE BEFORE THE NEXT INSPECTION.
08/21/2002 ELECTRIC - FINAL Denied GROUND RODS TO BE 30" HORZONTAL INSTALL MAIN GROUNDING ELECTRODE AT SERVICE NEUTRAL DESIGNATED ON EQUIPMENT PAPERWORK.-CABLE T.V. MUST BE OUT OF DEDICATED WORK SPACE AND REQUIRED CLEARANCE. NEED GROUND BUSH & BOND JUMPER FOR RISER.
08/05/2002 ELECTRIC - FINAL Partial Approval 2010 AND 2005 OK CABLE DROP BUT NO CLEARANCE FOR 511 #1, 511.#2. OWNER TO OBTAIN PERMITS FOR INSIDE CONST. PRIOR TO CLEARANCE FOR POWER.