Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0999*IMPROPER CLEARANCE IN FRONT OF SERVICE DUE TO CATV PEDESTAL INSTALLED. NO ACCESS TO BACK YARD INSIDE UNITS TO COMPLETE MY INSPECTION A RE-FEE IN DUE BEFORE THE NEXT INSPECTION. |
| 08/21/2002 |
ELECTRIC - FINAL |
|
Denied |
GROUND RODS TO BE 30" HORZONTAL INSTALL MAIN GROUNDING ELECTRODE AT SERVICE NEUTRAL DESIGNATED ON EQUIPMENT PAPERWORK.-CABLE T.V. MUST BE OUT OF DEDICATED WORK SPACE AND REQUIRED CLEARANCE. NEED GROUND BUSH & BOND JUMPER FOR RISER. |
| 08/05/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
2010 AND 2005 OK CABLE DROP BUT NO CLEARANCE FOR 511 #1, 511.#2. OWNER TO OBTAIN PERMITS FOR INSIDE CONST. PRIOR TO CLEARANCE FOR POWER. |