Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/12/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000*OK TO CLEAR. |
| 07/29/2002 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection 0000*1.) PLEASE VERIFY GROUND RODS 2.) GAS BOND IS TO BE TO INTERIOR SIDE PIPING 3.) AN APPROVED FITTING IS NEEDED FOR CONNECTION TO LB. AND SEALING DEVICE IS TO BE LISTED FOR FITTING 4.) PLEASE IDENTIFY NEUTRAL CLOSER TO WEATHER HEAD. |