Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T02EL01518
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/05/2002 | ELECTRIC - FINAL | Approved | IVRS - Inspection 0000* OK TO CLEAR OK CABLE DROP. | |
07/30/2002 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection 0000* | |
07/26/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES 1.) NO PHONE OR CABLE DROP CLEARANCE TILL CORRECTIONS MADE ON UNIT 2445 2.) NEED TO INSTALL #6 NEUTRAL FROM J-BOX UNDER CARPORT TO J-BOX BELOW SERVICE. 3.) CHECK J-BOX SIZE OR VERIFY 30 CU. IN. AS PER 370-16NEC. 4.) J-BOX UNDER CARPORT UNIT 2445 SHOULD BE W/P NOT 4 SQUARE WITH CAULKING TO SEAL BOX 5.) WHEN RE CALLING CALL FOR ALL THREE UNITS NOT JUST ONE. | |
07/25/2002 | ELECTRIC - FINAL | Denied | IVRS - Inspection 0245*NOTES NEUTRAL CONDUCTOR SIZE #6 IN EXISTING FEEDER TO BE CONTINUED TO SERVICE. 2.) CHECK J-BOX FOR CORRECT SIZE PER 370-16 NEC. 3.) CHASE NIPPLE AT 3/4" LB NOT ALLOWED. USE CLOSE NIPPLE WITH BOND BUSHING PER 250-94. |