Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/05/2002 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection 0000* OK TO CLEAR OK CABLE DROP. |
| 07/30/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* NOTES 1.) AS PER LAST INSP. WRITE UP, PVC BURIAL DEPTH IS 18", PVC CONDUIT NOT CONNECTED TO STEEL CONDUIT 300-5 NEC. 2.) CANNOT SPLICE COPPER CONDUCTORS TO ALUM, ON SAME SPLIT BOLT CONNECTOR 110-14. 3.) UNDERGROUND TO BE INSPECTED BEFORE NEC BURIAL. |
| 07/29/2002 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection 0000*DIRECT BURIAL DEPTH IS 24" PVC 18" 300-5 NEC. |
| 07/25/2002 |
ELECTRIC - FINAL |
|
Denied |
IVRS - Inspection 0245* NOTES BONDING LOCKNUT OR BUSHING REQUIRED ON 2" NIPPLE IN GUTTER. 250-94 NEC. 2.) SINGLE GANG BELL BOX TO SMALL FOR # 6 SPLICES. 370-16 NEC. 3.) FEEDER NEUTRAL IN J-BOX OUTSIDE FROM SUB PANEL HAS A #6 NEUTRAL MUST BE CONTINUED TO NEW SERVICE. 4.) SHEET METAL SCREWS NOT ALLOWED TO ATTACH GROUND LUG TO GUTTER ENCLOSURE. 250-8 NEC. 5.) NEED TO VERIFY GAS PIPE BONDING EACH UNIT. NOTE THAT UNITS ON SEPERATE METERS. 6.) GROUNDING ELECTRODE SYSTEM REQUIRED ON STRUCTURES OR BLDS SEPERATEFROM BLD WITH SERVICE 250-32 NEC. |